1001

CPU Down Error with Device Access Issue

Mitsubishi Electric · MELSEC System Q/L Series

¿Qué significa 1001 ?

The CPU module has experienced a runaway condition or failure, potentially due to electrical noise, a hardware fault, or (for Universal model QCPU) accessing outlying devices with device range checks disabled (SM237 = 1) during BMOV, FMOV, or DFMOV instruction execution. This error specifically affects QCPU and LCPU modules.

Causas comunes

  • Runaway or failure of CPU module.
  • Malfunctioning due to noise or other external reasons.
  • Hardware fault within the CPU module.
  • Universal model QCPU accessed outlying devices with device range checks disabled (SM237 = 1) during BMOV, FMOV, or DFMOV instruction execution.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Implement noise reduction measures for the control system environment.

  2. 2

    Reset the CPU module and attempt to RUN it again.

  3. 3

    If the same error is displayed again after resetting, diagnose for a CPU module hardware fault.

  4. 4

    For Universal model QCPU, check devices specified by BMOV, FMOV, and DFMOV instructions and correct device settings.