1102

RAM Error - Work/Standard/Extended RAM

Mitsubishi Electric · MELSEC System Q/L Series

¿Qué significa 1102 ?

The work area RAM in the CPU module, or the standard and extended RAM areas, are faulty. This diagnostic occurs at power ON, after a reset, or when an END instruction is executed.

Causas comunes

  • Faulty work area RAM in the CPU module.
  • Faulty standard RAM and/or extended RAM in the CPU module.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming supply voltage to the PLC's power supply module and verify it adheres to the specified voltage range.

  2. 2

    Inspect the CPU module to ensure it is correctly and securely seated in its base unit; re-seat the module firmly if any looseness is detected.

  3. 3

    Verify the status of the CPU module's backup battery (if present) using its status indicators, and measure its voltage if safely accessible and within specification.

  4. 4

    Inspect the CPU module, its base unit connector, and the backplane for any signs of physical damage, corrosion, or foreign material.

  5. 5

    Verify that the operating environment's temperature and humidity are within the specified limits for the MELSEC Q/L Series system.