Traduciendo...
E.PUE

Parameter unit disconnection

Mitsubishi Electric · A500 Inverter

¿Qué significa E.PUE ?

This function stops the inverter output if communication between the inverter and the Parameter Unit (PU) is suspended due to disconnection or successive communication errors. This occurs when Pr. 75 is set to "2", "3", "16", or "17" for reset/disconnection detection, or if Pr. 121 is "9999" (RS-485) and the number of retries is exceeded, or if communication breaks for the time set in Pr. 122.

Causas comunes

  • Communication cable disconnected or broken between parameter unit and main controller.
  • Faulty connection at the terminal block of the parameter unit or main controller.
  • Power supply failure to the parameter unit.
  • Parameter unit itself has failed or is not recognized by the system.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Securely fit the DU and PU operation panels to the inverter.

  2. 2

    Verify the setting of parameter Pr. 75.

  3. 3

    Check the value of Pr. 121 for RS-485 communication retry settings.

  4. 4

    Check the time set in Pr. 122 for communication break detection.

Ver todos los códigos en este manual (21)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric A500 Inverter