E.BE

Brake transistor alarm detection

Mitsubishi Electric · A500 Inverter

¿Qué significa E.BE ?

This function stops the inverter output if a fault occurs in the brake circuit, typically due to damaged brake transistors. When this alarm appears, the inverter power must be switched off immediately to prevent further damage to the unit.

Causas comunes

  • The internal brake transistor within the inverter has malfunctioned.
  • Over-voltage on the DC bus during deceleration, causing brake resistor activation.
  • Short circuit across the brake resistor or its terminals.
  • Internal failure of the inverter's power stage.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Reduce the load inertia (J) connected to the motor.

  2. 2

    Evaluate the frequency of braking operations; ensure it is within the inverter's specified limits.

  3. 3

    Replace the inverter unit if brake circuit damage is confirmed.