E.LF
Output phase failure protection
Mitsubishi Electric · A500 Inverter
¿Qué significa E.LF ?
This function stops the inverter output if one of the three phases (U, V, W) on the inverter's output side (load side) results in an open phase. It can also activate if the rated motor current is extremely lower than the rated inverter current, suggesting a mismatch or very light loading conditions.
Causas comunes
- One or more phases of the output power to the motor are disconnected.
- Internal inverter driver failure affecting one phase output.
- Loose or broken connection at the motor terminals.
- Faulty motor winding causing an open circuit in one phase.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the motor wiring for continuity between phases U-V, V-W, and U-W at the inverter output terminals.
- 2
Inspect the motor for internal faults that could cause an open phase.
- 3
Verify that the capacity of the used motor is not smaller than the inverter's capacity.
- 4
Check the setting of Pr. 251 (output phase failure protection selection).
Datos técnicos verificados. Última actualización: March 2026