E3104

Safety parameters validation error

Indramat · IndraDrive MPx02

¿Qué significa E3104 ?

The IndraDrive MPx02's integrated safety technology has detected an inconsistency or error during the validation of safety-related parameters. This indicates a potential breach or misconfiguration in the safety system, preventing safe operation and requiring immediate attention.

Causas comunes

  • Incorrect configuration of safety parameters (e.g., safety limits, operating modes) in the safety configuration tool.
  • Parameter corruption during download, saving, or power cycling.
  • Firmware mismatch between the safety control and standard control sections of the drive.
  • Internal diagnostics detecting a safety-critical anomaly or data inconsistency.
  • Attempt to load an incompatible safety configuration file.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Access the safety configuration tool for the IndraDrive MPx02 and perform a re-validation of all safety-related parameters.

  2. 2

    Verify that all safety parameters have been correctly configured and match the requirements of the machine's safety concept and risk assessment.

  3. 3

    If parameters were recently changed, revert to a previously validated safe configuration and re-test.

  4. 4

    Ensure that the firmware of the drive's safety section is compatible with the standard firmware version and the safety configuration tool.

  5. 5

    If validation continues to fail, it may indicate an internal hardware fault in the safety module. Contact Indramat safety service.