Undervoltage in power section
Indramat · IndraDrive MPx02
¿Qué significa E2816 ?
The IndraDrive MPx02 has detected an undervoltage condition within its internal power section, specifically on the DC bus. This means the DC link voltage has fallen below a safe operating threshold, which can occur due to insufficient incoming AC power or excessive current demand, impacting drive stability.
Causas comunes
- Low incoming AC mains voltage, leading to an insufficient DC bus voltage.
- Excessive power regeneration back into a non-regenerative supply, causing the DC bus to collapse (less common for undervoltage, usually overvoltage, but can occur with insufficient braking capacity).
- Sudden heavy load demand causing the DC bus voltage to sag transiently.
- Faulty internal DC bus capacitors or charging circuit.
- High-resistance connections in the main power circuit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the incoming AC mains voltage at the drive input and verify it is within the specified operating range, ensuring no upstream issues are causing low supply voltage.
- 2
Monitor the DC bus voltage (if accessible via diagnostics) to confirm the undervoltage condition and its behavior during operation.
- 3
Check all power connections to the IndraDrive MPx02 for looseness or corrosion, which could introduce resistance and voltage drops.
- 4
Verify the drive's configured mains voltage parameter (P-0-0120) matches the actual supply voltage.
- 5
If the mains voltage is stable and correct, but undervoltage persists, it may indicate an internal fault within the drive's power section, requiring service.