2926 C3E0

Err. in rated U of motor %.2s

Heidenhain · NC Control

¿Qué significa 2926 C3E0 ?

The motor rated voltage for the specified axis is outside of the permitted input range. This indicates a mismatch between the motor's specified voltage and the configured or available voltage.

Causas comunes

  • Motor rated voltage outside of permitted input range.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the rated voltage (U-rated) of the motor for the specified axis against the motor's nameplate data.

  2. 2

    Check the motor table entry in the NC control's parameters to ensure the rated voltage is correctly entered and matches the motor specifications.

  3. 3

    Measure the actual supply voltage provided to the motor drive to ensure it is stable and within the allowed operating range.

  4. 4

    Ensure the correct motor and drive combination is being used, suitable for the available power supply and machine configuration.