Heidenhain · NC Control

¿Qué significa 10591 E005 ?

The measured status of the '-SH1' signal is at a 'low' level and fails to change to the 'inactive' ('high' level) status, even though the MC (Motion Control) is triggering its corresponding watchdog. This points to an internal software error or hardware defect.

Causas comunes

  • The measured status of the "-SH1" signal is "low" level.
  • The "-SH1" signal does not change to the "inactive" ("high" level) status, although the MC is triggering the corresponding watchdog.
  • Internal software error.
  • Hardware defective.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Power cycle the NC control and related MC modules to reset the system and clear transient software errors.

  2. 2

    Inspect the wiring and connections of the -SH1 signal path, particularly where it interfaces with the MC unit, for damage or loose terminals.

  3. 3

    Check the MC module for any visible signs of damage, overheating, or component failure.

  4. 4

    Verify the safety software configuration related to the -SH1 signal and its interaction with the MC watchdog.

  5. 5

    If possible, use a multimeter or oscilloscope to monitor the -SH1 signal level during startup and operation to identify its state transitions.