Traduciendo...
506

Overvoltage on DC side (PV2)

Fronius · Primo GEN24

¿Qué significa 506 ?

The Fronius Primo GEN24 208-240 inverter has detected an excessively high voltage from the PV2 string on the DC side, exceeding its maximum input voltage rating. This poses a risk of damage to the inverter's DC-DC stage.

Causas comunes

  • Overvoltage on the DC side (PV2).
  • Incorrect PV array sizing (too many modules in series).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the PV2 string using the DC disconnector and measure the open-circuit voltage (Voc) of the PV2 string.

  2. 2

    Compare the measured Voc with the maximum DC input voltage specification for the Fronius Primo GEN24 208-240 inverter.

  3. 3

    Verify the number of PV modules in series for PV2; ensure it does not exceed the inverter's maximum voltage rating, especially at cold temperatures.

  4. 4

    Check for any miswiring or faulty components in the PV2 string that could result in an unexpectedly high voltage.

  5. 5

    If the array configuration is validated and within specifications, power cycle the inverter to clear the fault. If the error persists, contact Fronius service.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas