103

AC voltage too low

Fronius · Primo GEN24

¿Qué significa 103 ?

The AC grid voltage at the inverter's connection point has fallen below the permitted limits for the Fronius Primo GEN24 208-240 inverter. This can cause the inverter to disconnect from the grid, preventing proper power feed-in.

Causas comunes

  • The grid voltage is too low.
  • Impedance in the AC connection cable is too high (cable too long, cross-section too small).
  • The grid impedance is too high (local grid problem).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the AC grid voltage at the inverter's connection point with a multimeter and confirm it falls within the Fronius Primo GEN24 208-240 inverter's specified operating range.

  2. 2

    Examine the AC connection cable for appropriate length and cross-section; optimize if necessary to reduce impedance.

  3. 3

    Confirm all AC connections are tight and correctly terminated to minimize voltage drop.

  4. 4

    Contact the grid operator to investigate and resolve issues related to low grid voltage or high grid impedance in the local grid.

  5. 5

    Check the grid connection point for other large loads that might be causing voltage sags.