Traduciendo...
17

Serial communication timeout

Danfoss · VLT 2800 Variable Speed Drive

¿Qué significa 17 ?

No serial communication is being received by the adjustable frequency drive. This warning is active only when parameter 514 (Bus time interval function) is set to a value other than OFF. If set to 'Stop and trip', it will escalate from a warning to an alarm after a timeout.

Causas comunes

  • Loss of communication signal on the serial bus (e.g., RS-485, Modbus RTU) due to cable break or disconnection.
  • Incorrect communication parameters (e.g., baud rate P510, parity P511, address P512) configured in the drive or the master device.
  • Master device (PLC, HMI) stopped sending commands or is powered off.
  • Bus termination resistor missing or incorrectly set on the communication network, causing signal reflection.
  • Excessive electrical noise on the communication lines, interfering with data transmission.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the communication cable connections at the drive's serial port (e.g., RJ-45, terminal block) and at the master device.

  2. 2

    Confirm that the drive's communication parameters (P510, P511, P512, P514) match the master device's settings and network requirements.

  3. 3

    Check the master device (PLC, controller) status and program logic to ensure it is actively sending communication frames.

  4. 4

    Measure voltage levels on the communication bus lines (e.g., RS-485 A/B differential voltage) to confirm signal integrity using an oscilloscope.

  5. 5

    Inspect the communication bus for proper termination resistors at both ends of the segment.

  6. 6

    Temporarily disable or bypass potential noise sources (e.g., contactors, switching power supplies) to diagnose electromagnetic interference.

Ver todos los códigos en este manual (40)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT 2800 Variable Speed Drive