Two-Hand Discrepancy Error - Input Pair 2
Beckhoff · TwinSAFE Logic FB
¿Qué significa FB TWOHAND Bit 1 ?
A discrepancy has been detected within the two channels of input pair 2 for the FB TWOHAND. This means the redundant hand actuation signals are not synchronizing correctly, indicating a potential issue with the two-hand device, its wiring, or incorrect timing. This will prevent safe two-hand operation and put the machine into a safe state.
Causas comunes
- Wiring fault on one channel of input pair 2 (e.g., broken wire to input X5.1 or X5.2 on safety PLC).
- Malfunctioning two-hand actuation button for input pair 2, causing differing actuation/release times between channels.
- Electrical interference (EMI) on the signal lines of input pair 2, leading to false switching states.
- Degraded contact within the safety pushbuttons for input pair 2, resulting in intermittent signal loss.
- Discrepancy time parameter (e.g., P_TwoHandDiscTime) set too tight, causing false positives from normal button tolerance.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Power down the safety system, then use a multimeter to measure the resistance of the wiring from each button of input pair 2 to its respective safety input terminal (e.g., X5.1, X5.2).
- 2
2. With power restored, observe the diagnostic LEDs on the safety module for input pair 2 while actuating each button independently and simultaneously.
- 3
3. Replace the push button switch assembly for input pair 2 if its internal contacts show resistance instability or failure during actuation tests.
- 4
4. Inspect the shielded cabling for input pair 2; verify the shield is properly grounded at one end (e.g., control cabinet ground bar).
- 5
5. Access the safety controller's programming interface and temporarily increase the 'TwoHandDiscTime' parameter (e.g., to 500ms) to rule out overly sensitive timing.