0x401F

Press Not Moving After Start Command

Beckhoff · TwinSAFE Logic FB

¿Qué significa 0x401F ?

The PressStarted input was TRUE, commanding the press to move, but the position did not change (or 'Stopped' did not become FALSE) within the PressStartedDelayTime. This indicates a failure to initiate motion after the start command, potentially due to a mechanical jam or drive issue, preventing operation.

Causas comunes

  • Press mechanism did not move after receiving a start command.
  • Actuator or motor failed to engage.
  • Insufficient power supply to the drive system.
  • Mechanical obstruction preventing movement.
  • Faulty start command signal or logic.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the mechanical system for obstructions, jams, or insufficient power/force to initiate movement.

  2. 2

    Verify the motor, actuator, and associated power components for correct operation and wiring.

  3. 3

    Inspect the position sensor to ensure it is detecting movement correctly and not stuck at a fixed value.

  4. 4

    Review the PressStartedDelayTime parameter to ensure it is adequately set for the expected start-up sequence.