FB MUTING Bit 1

Muting Discrepancy Error - OSSD Input Group

Beckhoff · TwinSAFE Logic FB

¿Qué significa FB MUTING Bit 1 ?

A discrepancy has been detected in the OSSD (Output Signal Switching Device) input group (e.g., OssdIn1/OssdIn2) within the FB MUTING function block. These inputs typically come from a safety light curtain or area scanner. A discrepancy means the redundant OSSD signals are not synchronized, indicating a fault in the safety device or its wiring, compromising the primary safeguarding function and stopping the machine.

Causas comunes

  • Faulty or misaligned safety light curtain causing inconsistent OSSD output signals (OssdIn1, OssdIn2).
  • Wiring short-circuit or open-circuit on one or both OSSD input lines to the safety PLC (e.g., terminals X2.1, X2.2).
  • Electromagnetic interference (EMI) affecting the OSSD signal integrity during transmission to the safety controller.
  • Contamination or damage to the light curtain's emitter or receiver optics.
  • Parameter 'OSSDDiscTime' (e.g., P_OssdDiscTime) set too short for the actual OSSD signal delay.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Check the diagnostic indicators on the safety light curtain emitter and receiver for proper operation and alignment (e.g., green status LEDs).

  2. 2

    2. Power down the system, then perform a continuity test on the OSSD wiring from the light curtain outputs to the safety input terminals (e.g., X2.1, X2.2).

  3. 3

    3. With power restored, use an oscilloscope to measure the OSSD signals (OssdIn1, OssdIn2) at the safety PLC input terminals for synchronized switching behavior.

  4. 4

    4. Clean the protective windows of the safety light curtain emitter and receiver with a non-abrasive cleaner.

  5. 5

    5. Review and potentially increase the 'OSSDDiscTime' parameter (e.g., from 50ms to 100ms) in the safety controller configuration.

Ver todos los códigos en este manual (60)