Traduciendo...
FB ENVELOPE Value 1

Underflow (InValue below the envelope)

Beckhoff · TwinSAFE Logic FB

¿Qué significa FB ENVELOPE Value 1 ?

The input value (InValue) has fallen below the defined lower limit of the envelope in the FB Envelope function block. This indicates a deviation from the expected operating range, potentially causing the safety function to trip or behave unpredictably, leading to an unsafe state.

Causas comunes

  • Analog sensor (e.g., pressure, flow, temperature) reading below its expected operating range due to calibration drift or process upset.
  • Incorrect lower limit parameter (e.g., P1-05) set too high within the FB Envelope function block configuration.
  • Signal conditioning error causing the input value to be attenuated below the envelope's lower threshold (e.g., faulty isolator).
  • Loss of input signal (e.g., 4-20mA sensor wire broken, resulting in 0mA) interpreted as an underflow condition.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Measure the actual process variable (PV) and compare it to the 'InValue' displayed in the safety logic.

  2. 2

    2. Verify the analog sensor's output (e.g., 4-20mA, 0-10V) directly at the input terminals of the safety module (e.g., EL3xxx terminal X1).

  3. 3

    3. Check the 'Lower Limit' parameter (e.g., P1-05) within the FB Envelope configuration for correct scaling and value.

  4. 4

    4. Calibrate the associated analog sensor according to manufacturer specifications.

  5. 5

    5. Inspect the signal wiring from the sensor to the safety module for damage or loose connections, particularly ground and shield integrity.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Beckhoff TwinSAFE Logic FB