Traduciendo...
0x40CA

InValue Error (Specific)

Beckhoff · TwinSAFE Logic FB

¿Qué significa 0x40CA ?

The 'InValueError' flag within the FB Envelope function block is TRUE, indicating a specific issue with the input value. This signifies that the input signal is not valid or within the expected operational parameters, forcing the FB into a safe state. The fault provides the FB instance and the current InValue for diagnosis.

Causas comunes

  • Analog input signal is erratic or noisy, causing transient values outside the expected operating window (e.g., EMI from nearby VFD).
  • Sensor provides an invalid or 'stuck' reading that falls outside the configured 'MinValid' and 'MaxValid' thresholds (e.g., P4-01, P4-02).
  • Discrepancy detected between redundant analog inputs if configured, exceeding allowed deviation (e.g., P4-03 difference).
  • Internal diagnostics of the analog safety input module (e.g., EL3102) detect an issue with the measurement path.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Monitor the raw input signal (e.g., InValue) using a high-speed oscilloscope at the input terminals of the safety module (e.g., EL3xxx terminal X3).

  2. 2

    2. Verify the sensor's output against a calibrated reference instrument.

  3. 3

    3. Check the 'MinValid' (P4-01) and 'MaxValid' (P4-02) parameters in the FB Envelope configuration for correct range settings.

  4. 4

    4. Ensure proper grounding and shielding of the analog input cable to minimize electrical noise.

  5. 5

    5. Check for any internal diagnostic flags on the analog input safety module (e.g., EL3102) itself via TwinCAT System Manager.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Beckhoff TwinSAFE Logic FB