F48
Params Defaulted
Allen-Bradley · PowerFlex 4 Adjustable Frequency
¿Qué significa F48 ?
This fault indicates that the drive has either been commanded to restore factory default values to its EEPROM, or a corruption of parameter data occurred spontaneously. This resets all configurable parameters.
Causas comunes
- Power loss or incorrect parameter save operation.
- Factory reset or parameter initialization performed.
- EEPROM or memory corruption affecting parameter storage.
- Parameter load failure from external source.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Clear the fault by pressing the Stop key, cycling power to the drive, or setting parameter A100 [Fault Clear] to option 1 ('Reset Fault') or 2 ('Clear Buffer').
- 2
Reprogram all necessary drive parameters to their application-specific values after the defaults have been written.
Datos técnicos verificados. Última actualización: March 2026