Hardware Preservation Fault (High Internal Temperature)
Allen-Bradley · Logix 5000 Controllers
¿Qué significa Hardware Preservation Fault ?
This fault is declared by the controller when internal module temperatures exceed a critical threshold, leading to a reset and immediate power disablement. The OK status indicator illuminates red, and the module remains unpowered until it cools below the Hardware Preservation Hysteresis limit. Subsequently, the module enters fault mode, logs the event, and displays 'CPU Temperature Fault' on the front panel. For 5580 controllers, this can be indicated by a flashing green OK status.
Causas comunes
- Internal module temperature exceeding the hardware preservation threshold
- Inadequate cooling of the controller module
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the ambient temperature within the control panel enclosure using a calibrated thermometer
- 2
Visually inspect controller heatsinks and cooling vents for dust accumulation or obstructions
- 3
Verify the operational status of any enclosure cooling fans or air conditioning units, confirming proper setpoints
- 4
Check for proper airflow pathways around the controller module within the chassis/panel