HandFBFaulted (Status1.3)

Hand Feedback Value Health Bad

Allen-Bradley · Logix 5000 Controllers

¿Qué significa HandFBFaulted (Status1.3) ?

This fault indicates that the Hand Feedback (Tieback) value health is bad. This occurs if the Hand FB value quality is bad, the value is invalid, or there's a communication fault with the input. In the PPID instruction, Sts_HandFdbkBad is also set if Inp_HandFdbk value is Infinite (Inf), Negative Infinite (-Inf), or Not-a-Number (NaN).

Causas comunes

  • Hand Feedback (Tieback) value quality is bad or unreliable
  • Invalid Hand Feedback value (e.g., Inf, -Inf, or NaN for PPID)
  • Communication fault with the Hand Feedback input module or source
  • Inp_HandFdbkBad input (for PPID) is asserted

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the Hand Feedback input signal at its source terminals using a multimeter or process calibrator

  2. 2

    Check the communication status of the Hand Feedback input module in the I/O tree

  3. 3

    Confirm that the Hand Feedback device is providing a valid, numerical, in-range signal

  4. 4

    Review the logic driving Inp_HandFdbkBad (for PPID) to ensure it is not erroneously asserted

Ver todos los códigos en este manual (17)