Error Applying Mint Motion Library Command
ABB · Application Error ABB Motion Drives Error trouble shoo
¿Qué significa b06410 ?
This error occurs during or after a firmware upgrade when parameters are re-instated. It typically indicates that the new firmware version has introduced a new parameter that was not present in the old parameter file, preventing proper configuration.
Causas comunes
- Incompatibility between an old parameter file and a newly upgraded firmware version due to new parameters.
- The drive's parameter file (PTX) is corrupted or contains invalid data for the new firmware.
- Incomplete or failed firmware upgrade process.
- Attempting to apply parameters from a different drive model or firmware version.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Connect Mint WorkBench to the drive, access the command line, and enter the "FDF" or "FACTORYDEFAULTS" command.
- 2
Power cycle the drive (note that the IP address will return to 192.168.0.1 after factory defaults).
- 3
Re-commission the drive from scratch using Mint Workbench, ensuring all parameters are set correctly for the new firmware.
- 4
Alternatively, download a previously saved parameter (PTX) file that is known to be compatible with the current firmware version.