Traduciendo...
10019

Motor temperature trip (_ecMOTOR_TEMP_INPUT)

ABB · Application Error ABB Motion Drives Error trouble shoo

¿Qué significa 10019 ?

An over temperature condition has been detected for the motor. This can be triggered either by the hardwired X10 thermistor input or by a serial motor encoder (e.g., Hiperface DSP) providing thermistor resistance data. The drive trips if this value exceeds the MOTORTEMPERATURETRIP parameter.

Causas comunes

  • Motor over temperature condition.
  • Faulty or incorrectly wired PTC thermistor sensor connected to X10 input.
  • Incorrect MOTORTEMPERATURETRIP parameter setting for motors with serial encoders (like Hiperface DSP).
  • Issues with the feedback cable or wiring providing thermistor data, especially with serial encoders.
  • Using a motor without a PTC thermistor or with a switch that does not go open-circuit at high temperatures, causing incorrect trip behavior.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the motor for signs of overheating; allow it to cool and investigate the mechanical load or duty cycle if actual over-temperature is confirmed.

  2. 2

    For hardwired thermistor inputs (X10), verify the wiring and connections of the PTC thermistor to terminals TH1 and TH2.

  3. 3

    For motors with serial encoders, verify the MOTORTEMPERATURETRIP parameter is set to a resistance suitable for the motor's thermistor device (e.g., MOTORTEMPERATURETRIP(0) = 1200).

  4. 4

    Check the feedback cable and wiring for damage, shorts, or loose connections that could affect temperature feedback data, regardless of the feedback type.

  5. 5

    If temperature monitoring is not desired or applicable, ensure a wire link (short-circuit) is installed between X10 terminals TH1 and TH2 to suppress the hardwired thermistor trip function.

Ver todos los códigos en este manual (58)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Application Error ABB Motion Drives Error trouble shoo