Uv2

Control Power Supply Undervoltage

Yaskawa · P1000

What does Uv2 mean?

The drive detected an undervoltage condition specifically in the control power supply circuit. This affects the internal logic and control functions of the drive.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the main input voltage (L1-L2, L2-L3, L3-L1) at the drive's R/L1, S/L2, T/L3 terminals and verify against the nominal supply voltage.

  2. 2

    Inspect all main power input wiring connections at the drive terminals and upstream power distribution for looseness, corrosion, or signs of damage.

  3. 3

    Verify drive parameters related to input voltage settings and undervoltage trip levels (e.g., L1-01, L2-01) match the actual system supply and electrical drawings.

  4. 4

    If the drive utilizes a separate auxiliary control power input (e.g., 24VDC or 110VAC control source), measure its voltage at the dedicated terminals and confirm it is within specified operating limits.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults