AL14

Serial Communications Alarm

Yaskawa · P1000

What does AL14 mean?

This alarm indicates a serial communications issue. It is shown when parameter BO 11 (Communication Fault Enable) is enabled and parameter AO 22 (Cable Loss Speed) is set to a value other than 0, allowing the drive to continue at the last speed.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the serial communication cable between the Yaskawa P1000 drive and the master control device for physical damage, proper routing, and secure connections at both ends.

  2. 2

    Verify all serial communication parameters (e.g., baud rate, data bits, parity, stop bits, drive address) in the Yaskawa P1000 drive's configuration match those set in the master communication device.

  3. 3

    Check the termination resistors and biasing settings on the RS-485 communication network to ensure they are correctly applied according to the network topology and drive manual.

  4. 4

    Verify proper grounding and shielding of the serial communication cable and network infrastructure to prevent electromagnetic interference (EMI) from disrupting communication.

  5. 5

    Monitor the communication status indicators (e.g., LEDs, status screens) on both the Yaskawa P1000 drive and the master communication device for activity, errors, or timeouts.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Yaskawa AL14 — How to resolve: Serial Communications Alarm | ErrorLib