CPF22

A/D Conversion Fault

Yaskawa · P1000

What does CPF22 mean?

A fault occurred within the analog-to-digital conversion circuitry of the drive. This affects the accuracy of input signal readings from sensors and other analog sources.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect all analog input wiring (signal and return) for proper shielding, secure connections, and absence of damage or corrosion at both the sensor and drive terminals.

  2. 2

    Measure the actual analog input signal (e.g., voltage or current) directly at the drive's input terminals using a multimeter or oscilloscope, and compare to expected values and stability.

  3. 3

    Verify drive parameters related to analog input configuration, scaling, offset, and filtering (e.g., A1-xx for P1000) match the connected sensor type and desired application.

  4. 4

    Inspect the drive's control power supply grounding and the integrity of the overall panel grounding connections to minimize potential noise or interference.