Er - 01

Auto-tuning Data Error

Yaskawa · E7 Drive

What does Er - 01 mean?

An error was detected in the data input for auto-tuning or in the relationship between the motor output and motor rated current. This prevents successful auto-tuning, which is crucial for optimal drive performance and motor control.

Common Causes

  • Incorrect motor nameplate data (e.g., motor rated current, rated voltage, rated speed) entered into drive parameters (P3-01 to P3-05).
  • Motor not connected or incorrect wiring between drive output terminals (U, V, W) and motor terminals.
  • Significant mismatch between the drive's rated output and the motor's actual power rating.
  • Motor overload or mechanical binding preventing the motor from moving freely during the tuning process.
  • Encoder feedback issue (if using closed-loop auto-tuning) preventing accurate speed/position measurement.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify all motor nameplate data entered into drive parameters (e.g., P3-01 (Motor Rated Current), P3-02 (Motor Rated Voltage)) for accuracy.

  2. 2

    2. Confirm wiring continuity and correct phase sequence between drive output terminals (U, V, W) and motor terminals.

  3. 3

    3. Ensure the motor shaft is free to rotate without mechanical binding or excessive load during the auto-tuning sequence.

  4. 4

    4. Check for proper grounding of the motor frame and drive to prevent measurement inaccuracies.

  5. 5

    5. Attempt to run the motor in manual mode (without auto-tuning) at a low frequency (e.g., 5 Hz) to confirm basic operation.

  6. 6

    6. If using an encoder, verify encoder wiring integrity and signal presence at the feedback option card terminals.

Browse all codes in this manual (64)
Verified technical data. Last updated: March 2026

Related Faults