SCF5

Load Short-Circuit (Igon Load Sequence)

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

What does SCF5 mean?

A hard detection of a load short-circuit during the Igon load sequence. This implies a short circuit condition was detected at the motor output during the drive's internal initialization or measurement sequence, indicating a problem with the motor or its wiring before full operation.

Common Causes

  • Short circuit between motor phases or phase-to-ground detected during the drive's initial power-up or pre-magnetization sequence (Igon).
  • Motor cable insulation breakdown occurring at cold start or during initial current injection for motor identification.
  • Faulty motor winding causing an immediate short when even a small current is applied.
  • Incorrect motor parameter settings (e.g., motor type, nominal current) leading to an erroneous short detection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect the motor cables from the drive's output terminals (U, V, W).

  2. 2

    2. Use a megohmmeter to measure insulation resistance between motor phases and from each phase to ground (PE) with the motor cold.

  3. 3

    3. Use a low-resistance ohmmeter to measure winding resistance between motor phases (U-V, V-W, W-U); compare to nameplate data.

  4. 4

    4. Power up the drive with no motor connected and verify it clears the SCF5 fault.

  5. 5

    5. Review drive parameters (e.g., P0-01 to P0-10) for correct motor type, voltage, current, and frequency settings.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Schneider Electric Altivar Machine ATV320 Variable Speed Drive