SCF4

IGBT Short-Circuit (Hard Detection)

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

What does SCF4 mean?

A hard detection of an IGBT short-circuit. This indicates a severe internal failure of the Insulated Gate Bipolar Transistor (IGBT) within the drive's power stage. This is a critical hardware fault that can cause catastrophic damage to the drive and is usually not field-repairable.

Common Causes

  • Internal failure of an Insulated Gate Bipolar Transistor (IGBT) within the drive's inverter bridge.
  • Voltage spikes on the DC bus exceeding the IGBT's breakdown voltage, possibly due to improper braking resistor sizing.
  • Overcurrent condition causing thermal stress and eventual failure of the IGBT junction.
  • External short circuit at motor terminals (U, V, W) that the drive's protection circuit failed to clear quickly enough.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect incoming AC power from the drive's input terminals (L1, L2, L3) and wait for DC bus discharge (0VDC).

  2. 2

    2. Disconnect motor cables from the drive's output terminals (U, V, W).

  3. 3

    3. Use a diode test function on a multimeter to check the rectifier (input L1/L2/L3 to DC bus) and inverter sections (DC bus to output U/V/W).

  4. 4

    4. Look for visible signs of damage (e.g., burn marks, bulging components) on the drive's power board.

  5. 5

    5. If diode test indicates shorted IGBTs, consider the drive as requiring replacement or professional repair.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Schneider Electric Altivar Machine ATV320 Variable Speed Drive