Direct Ground Short-Circuit (Hard Detection)
Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
What does SCF3 mean?
A hard detection of a direct ground short-circuit. This indicates a severe fault where a motor phase or internal component is directly shorted to earth ground. This condition poses a significant safety hazard and can cause severe damage to the drive. This fault can be manually cleared if the 'Reset restricted fault configuration' (HrFC) parameter is set to 'Yes'.
Common Causes
- Motor phase wire directly shorted to the motor frame or earth ground due to insulation failure.
- Internal wiring within the drive or motor starter shorted directly to chassis ground.
- Significant water ingress or conductive foreign material bridging a phase conductor to ground.
- Damaged motor cable insulation causing a direct short from a phase conductor to conduit or machine frame.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Disconnect all motor phases (U, V, W) from the drive output terminals.
- 2
2. Use a megohmmeter to measure insulation resistance from each motor phase (U, V, W) to the motor frame ground (PE).
- 3
3. Visually inspect the motor terminal box for moisture, debris, or damaged wire insulation.
- 4
4. Inspect the entire length of the motor cable for insulation damage, pinch points, or water ingress.
- 5
5. If the motor and cable test clear, power down and check for internal drive wiring shorting to its chassis.