EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Troubleshooting Course
  4. E.P24
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.P24

24 VDC Power Output Short Circuit

Mitsubishi Electric · FR-A800 Troubleshooting Course

What does E.P24 mean?

This fault indicates a short circuit on the FR-A800 inverter's internal or external 24 VDC power supply output, typically used for control circuit power or external sensors. The inverter trips to protect its internal power supply and connected devices.

Common Causes

  • Short circuit in the wiring connected to the FR-A800 inverter's 24 VDC output terminals (e.g., between 24V and SD).
  • Faulty external sensor, relay, or control device connected to the 24 VDC supply.
  • Internal short circuit within the inverter's control circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect all external devices and wiring from the FR-A800 inverter's 24 VDC output terminals (usually 24V and SD).

  2. 2

    Measure the voltage at the inverter's 24 VDC output terminals. If the fault clears with nothing connected, the issue is external.

  3. 3

    Reconnect external devices one by one, checking for the fault after each connection to identify the specific faulty device or wiring section.

  4. 4

    Inspect all control wiring for insulation damage, pinched wires, or foreign material causing a short.

  5. 5

    If the fault persists even with all external connections removed, the FR-A800 inverter itself may have an internal fault requiring service.

Browse all codes in this manual (16)
Verified technical data. Last updated: April 2026

Related Faults

E.CDOOutput Current Detection Value ExceededE.IPFInstantaneous Power FailureE.LFOutput Phase Loss
Source: Mitsubishi Electric FR-A800 Troubleshooting Course
Open Manual (Page 4)Search more codes in this manual