Mitsubishi Electric · FR-A800 Troubleshooting Course
This fault occurs when an incompatible or non-existent regenerative option is selected in parameter E300 (Pr.30), such as a high-efficiency converter or power supply regeneration common converter, but no such option is connected or detected by the FR-A800 inverter. The inverter will trip to prevent incorrect operation.
Click steps to track your progress.
Verify parameter E300 (Pr.30) (Regenerative function selection) matches the installed hardware. If no external regenerative option is connected, set E300 (Pr.30) to '0' (built-in brake).
If a regenerative option is installed, inspect its wiring and connections to the FR-A800 inverter for looseness or damage.
Consult the manual for the specific regenerative option for its diagnostic indicators and troubleshooting.
If the issue persists after verifying settings and connections, consider replacing the regenerative option unit or the inverter if the fault points to internal issues.