EPM data: firmware type incompatible
Lenze · i550 Protec Drive
What does 30353 mean?
The parameter settings saved in the memory module are incompatible with the firmware type of the inverter, for example, using an application-specific IO module's memory in a standard IO inverter. This prevents proper operation.
Common Causes
- The EPM contains parameters configured for an application-specific firmware type (e.g., hoist, elevator, specific process control) inserted into a standard firmware type inverter.
- Mismatch between the inverter's internal hardware configuration (e.g., specific option cards, motor type) and the 'firmware type' saved on the EPM.
- Attempting to use an EPM that was configured for a safety-integrated drive variant in a non-safety standard inverter.
- The EPM's saved hardware profile or device identification does not match the actual hardware configuration of the inverter.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Verify the specific 'firmware type' of the inverter (often displayed on the HMI or in P-parameters) and compare it against the intended type for the EPM.
- 2
2. Ensure the EPM used is for the standard firmware version of the inverter, or if the drive is application-specific, ensure the EPM matches that specific application.
- 3
3. Back up the current drive parameters, then perform a factory reset (e.g., P99.02=1 for defaults) to clear incompatible settings and re-download the correct parameters.
- 4
4. Use the drive's software tool to compare the EPM's saved configuration with the actual hardware configuration detected by the inverter, identifying discrepancies.
- 5
5. Replace the EPM with a new module that is blank or contains a parameter set specifically created for the inverter's current firmware type and hardware configuration.