0x2340

Short circuit at the motor end

Lenze · i550 Protec Drive

What does 0x2340 mean?

This fault indicates a short circuit specifically in the motor cable. When detected, the inverter immediately disables the drive, leading to the motor coasting without torque.

Common Causes

  • Direct phase-to-phase short circuit within the motor cable due to insulation damage (e.g., crushing, abrasion).
  • Loose strands of motor cable wire bridging two phases at the inverter output terminals or motor input terminals.
  • Internal motor winding short circuit (turn-to-turn or phase-to-phase) within the motor itself.
  • Contamination (e.g., metal filings, conductive liquids) creating a short path at the motor's terminal box.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    De-energize the drive and lock out power at the main disconnect.

  2. 2

    Disconnect the motor cable from both the inverter output terminals (U, V, W) and the motor input terminals (U1, V1, W1).

  3. 3

    Measure continuity between each phase conductor (U, V, W) of the motor cable using a multimeter; expect infinite resistance (open circuit).

  4. 4

    Visually inspect the entire length of the motor cable for any external damage, cuts, or crushing that could compromise insulation.

  5. 5

    Inspect inverter terminal blocks and motor terminal box for stray wire strands, debris, or improper wiring that could cause a short.

  6. 6

    Measure the resistance between motor phases (U1-V1, U1-W1, V1-W1) at the motor terminals to verify winding integrity; expect balanced, low resistance readings.