F226
Undervoltage Error
Indramat · ECODRIVE Controller
What does F226 mean?
The drive controller monitors the DC bus voltage. If the DC bus voltage falls below a predefined minimal threshold, the drive independently shuts down, triggering the configured error reaction. This protects the drive from operation with insufficient power.
Common Causes
- The power source has been interrupted without first switching off the drive enable (RF) signal.
- Disturbance or sag in the main power supply.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the logic and sequence of operations for the drive enable (RF) signal within the connected control system, ensuring it is removed before the power source is interrupted.
- 2
Check the main power supply voltage to the drive controller for stability and correct levels.
- 3
Measure the DC bus voltage during operation to identify any sags or interruptions.
- 4
Ensure the control enable signal is removed to clear the error.
Verified technical data. Last updated: March 2026
Related Faults
Source: Indramat ECODRIVE Controller