E250
Heatsink Overtemperature Warning
Indramat · ECODRIVE Controller
What does E250 mean?
The temperature of the heatsink in the ECODRIVE DKC01.1/DKC11.1 drive controller has reached the maximum allowable warning temperature. The drive continues to follow the command value for 30 seconds, allowing for a controlled shutdown before an F218 shutdown occurs.
Common Causes
- Deficiency of the drive's internal blower.
- Deficiency of the control cabinet’s climate control.
- Incorrect control cabinet dimensioning regarding the head ventilation.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Reduce the ambient temperature, for example, by improving control cabinet cooling.
- 2
Remove any obstruction or dirt from the ECODRIVE DKC01.1/DKC11.1 drive's heatsink.
- 3
Verify the control cabinet dimensions and ventilation for proper airflow, ensuring the drive is installed vertically.
- 4
If the internal blower is failing, prepare for drive controller replacement as a shutdown (F218) will occur soon.
Verified technical data. Last updated: March 2026
Related Faults
Source: Indramat ECODRIVE Controller