Earth Fault
Vacon · NX Liquid-Cooled Drive
Was bedeutet 3 ?
The current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to ground. This fault is most commonly caused by insulation failure in the motor cables or within the motor windings themselves.
Häufige Ursachen
- Insulation failure in motor windings or power cables.
- Ground fault in the connected equipment.
- Moisture or contamination ingress into electrical components.
- Faulty grounding connection.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the insulation resistance between each motor phase cable (U, V, W) and ground (PE) using a megger.
- 2
Measure the insulation resistance between each motor winding (U, V, W) and the motor frame (PE) with a megger.