10

Input Phase Failure

Vacon · NX Liquid-Cooled Drive

Was bedeutet 10 ?

An external electronic monitoring relay has detected an undervoltage, incorrect phase sequence, or a phase failure in the input line. The minimum threshold values are 360Vac for 400-500Vac supply and 470Vac for 525-690Vac supply, with a 0.1-second response delay. Possible causes include a missing supply phase, a blown supply fuse, incorrect mains cabling, or a grid interruption. Subcodes S1 (phase supervision diode supply) and S2 (phase supervision active front end) are available.

Häufige Ursachen

  • Loss of one or more phases on the main AC power input (P0303).
  • Internal rectifier failure.
  • Loose or disconnected input power wiring.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the settings of the External Monitoring Device (EMD) relay for correct undervoltage thresholds, phase sequence, and response delay.

  2. 2

    Verify the signal wiring from the EMD relay to the control unit.

  3. 3

    Measure the incoming supply voltage at the drive input terminals across all three phases.

  4. 4

    Check all input fuses for continuity and proper rating.

  5. 5

    Inspect the mains cabling for correct phase connections and signs of damage.

  6. 6

    Check the rectifying bridge for proper operation.