31
IGBT Over-temperature (Hardware)
Vacon · NX All-in-One Application
Was bedeutet 31 ?
The IGBT Inverter Bridge's over-temperature protection has activated, indicating excessively high short-term overload current. This typically points to the motor drawing too much current, potentially due to incorrect sizing or heavy load conditions, causing the inverter's power semiconductors to overheat.
Häufige Ursachen
- The temperature of the Insulated-Gate Bipolar Transistors (IGBTs) has exceeded the hardware limit.
- Inadequate cooling (fan failure, blocked heatsink) causing IGBT overheating.
- Overcurrent or overvoltage stress on the power electronics.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect the motor's current loading and reduce if exceeding nominal values.
- 2
Verify the motor's nominal current and power against the AC drive's rating to ensure proper sizing.
- 3
Perform an identification run to optimize motor parameters and drive control.