Übersetzen...
10

Input line supervision

Vacon · NX All-in-One Application

Was bedeutet 10 ?

An input line phase is missing, indicating a loss of one or more phases in the AC supply to the drive. This could be due to an open circuit in the supply cabling, a blown fuse, or a power distribution issue. Operating with a missing phase can damage the drive's input rectifier.

Häufige Ursachen

  • Input AC power phase is missing or unbalanced.
  • Faulty input power rectifier or smoothing circuit.
  • Loose connection on the AC input terminals.
  • External power source fluctuation.
  • Overload on the input stages.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the phase-to-phase and phase-to-neutral supply voltages at the drive's input terminals — verify all phases are present and balanced.

  2. 2

    Inspect all input fuses for continuity and ensure they are of the correct type and rating.

  3. 3

    Physically check the supply cables connecting to the drive for any signs of damage, loose connections, or disconnections at the terminal block.

Alle Codes in diesem Handbuch durchsuchen (42)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Vacon NX All-in-One Application