29

Thermistor Fault

Vacon · NX All-in-One Application

Was bedeutet 29 ?

The option board's thermistor input has detected an increase in motor temperature, indicating potential overheating. This can also be triggered by a faulty thermistor connection or if the input is left open when not in use.

Häufige Ursachen

  • The temperature sensor (thermistor) for motor or drive is out of range or disconnected.
  • Faulty thermistor or wiring to the temperature sensor.
  • Temperature readings indicate an abnormal condition.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the motor's cooling system for obstructions or malfunctions.

  2. 2

    Verify the motor's current loading against its nominal specifications.

  3. 3

    Examine the thermistor connection to the option board for looseness or damage.

  4. 4

    If the thermistor input on the option board is not utilized, ensure it is properly short-circuited.

Alle Codes in diesem Handbuch durchsuchen (42)