Übersetzen...
2

Overvoltage

Vacon · NX All-in-One Application

Was bedeutet 2 ?

A hardware trip (S1) has detected the DC-link voltage exceeding its safe limits. This can be caused by a deceleration time that is too short, high voltage spikes on the input power supply, or a rapid Start/Stop sequence. Subcode S2 indicates issues with overvoltage control supervision.

Häufige Ursachen

  • Input voltage exceeds the maximum allowable limit (e.g., P1-12 > 480V).
  • Power surge from the electrical grid.
  • Faulty power supply unit generating excessive voltage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Increase the deceleration time parameter in the drive settings to allow for slower motor braking.

  2. 2

    If regenerative energy is an issue, consider installing an optional brake chopper and brake resistor system.

  3. 3

    Activate or verify the settings of the drive's internal overvoltage controller.

  4. 4

    Measure the input voltage at the drive's main power terminals to ensure it is within specified limits and stable.

Alle Codes in diesem Handbuch durchsuchen (42)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Vacon NX All-in-One Application