Übersetzen...
82

Output Open Detected

SEW Eurodrive · MOVIFIT SC

Was bedeutet 82 ?

This fault signifies that the measured output current for either drive 1 or drive 2 is less than 2% of the unit's nominal current (IN,unit/device) when the respective drive is enabled. This strongly suggests an open circuit in the motor circuit, such as a disconnected or broken motor cable, a faulty motor winding, or an issue with the drive's output stage itself. This condition prevents motor operation and could indicate significant wiring or motor damage, posing a risk of component failure if the unit attempts to drive into an open circuit.

Häufige Ursachen

  • Open circuit in one or more motor phases (U, V, W) due to a broken wire in the motor cable.
  • Poor or loose connection at the motor terminal block or the drive's output terminals (U1/V1/W1 or U2/V2/W2).
  • Motor winding has an open circuit (e.g., internal break), preventing current flow despite the drive being enabled.
  • No motor connected to the drive output while the drive is enabled and attempting to run a motor.
  • Internal fault within the MOVIFIT unit's current measurement circuitry for the specific drive output.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the resistance of each motor winding (U-V, V-W, W-U) using a multimeter and compare to specified values (e.g., from motor nameplate or manual).

  2. 2

    Verify continuity of each motor phase cable (U, V, W) from the MOVIFIT output terminals to the motor terminal block using a multimeter.

  3. 3

    Inspect and tighten all connections at the MOVIFIT output terminals (U1/V1/W1 or U2/V2/W2) and the motor terminal block.

  4. 4

    Ensure a motor is actually connected and correctly wired to the drive output before enabling the drive.

  5. 5

    Check drive parameters related to minimum current detection thresholds (if adjustable, e.g., P303 for min current threshold) to ensure they are appropriate.

Alle Codes in diesem Handbuch durchsuchen (18)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes