Übersetzen...
1

Motor Overcurrent

SEW Eurodrive · MOVIFIT SC

Was bedeutet 1 ?

This fault signifies that the output current to either drive 1 (monitored by P300/P301) or drive 2 (monitored by P310/P311) has exceeded its configured cut-off limit for the parameterized delay time. This protective shutdown is often caused by excessive mechanical load on the motor, a short circuit in the motor windings or cables, or improperly set overcurrent parameters. Persistent overcurrent can lead to motor winding damage, thermal stress on cables, and potential failure of the MOVIFIT unit's output stage. If left unaddressed, this could result in costly motor replacement or unit downtime.

Häufige Ursachen

  • Excessive mechanical load on the motor, causing sustained current draw above the drive's configured limit (P300/P301 for drive 1, P310/P311 for drive 2).
  • Short circuit or ground fault in the motor windings or motor cable insulation, leading to uncontrolled current flow.
  • Incorrect motor parameters (e.g., motor nominal current P302) configured in the MOVIFIT unit, resulting in an inaccurate overcurrent trip threshold.
  • Mechanical jamming or binding in the driven machinery (e.g., conveyor, pump) preventing free movement and increasing motor torque demand.
  • Drive output stage (e.g., IGBTs) hardware failure causing an uncontrolled current surge.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the actual motor current for drive 1 (terminals U1/V1/W1) and drive 2 (terminals U2/V2/W2) using a true-RMS clamp meter and compare to P300/P301/P310/P311 settings.

  2. 2

    Check for mechanical obstructions or excessive friction in the connected machinery by manually rotating the motor shaft (with power off).

  3. 3

    Verify motor insulation resistance using a megohmmeter (500VDC) between each motor phase and ground, and between phases.

  4. 4

    Review drive parameters P300, P301 (Drive 1) and P310, P311 (Drive 2) to ensure the overcurrent trip limits are correctly set for the motor and application.

  5. 5

    Inspect motor cables for visible damage, kinks, or signs of insulation breakdown along their entire length and at termination points.

  6. 6

    Perform a controlled test run with no load to confirm motor current readings are within expected limits.

Alle Codes in diesem Handbuch durchsuchen (18)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes