Thermal Overload of Brake Coil / Defective Brake
SEW Eurodrive · MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc
Was bedeutet 89 ?
This fault indicates a thermal overload of the brake coil or a defect within the brake itself, including incorrect connection. Overtemperature can lead to reduced braking force, premature wear, or complete failure of the brake mechanism.
Häufige Ursachen
- Ramp time set too short, causing excessive brake engagement/disengagement cycles or slippage.
- Defective brake coil.
- Incorrect connection of the brake coil.
- Incorrect combination of the drive (brake coil) and MOVIMOT inverter.
- Incorrect setting of DIP switch S1/6 for 'MOVIMOT and motor with one lower power rating' combinations.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Increase the set ramp time to reduce brake stress.
- 2
Perform a brake inspection (refer to 'DR/DV/DT/DTE/DVE Series AC Motors' operating instructions').
- 3
Check the brake coil connection for correct wiring and integrity.
- 4
Check the combination of the drive (brake coil) and MOVIMOT inverter if the fault is signaled shortly after the first enable.
- 5
For 'MOVIMOT and motor with one lower power rating' combinations, check the setting of DIP switch S1/6.
- 6
Reset the fault by switching off and then switching on the DC 24V supply voltage.