Übersetzen...
F014

1 Output phase loss

Schindler · Easy Altivar ATV310 Drive

Was bedeutet F014 ?

For the ATV310 drive, this fault is detected when one phase on the drive's output to the motor is lost. This can be caused by poor electrical connections, damaged motor cables, or issues with a downstream contactor.

Häufige Ursachen

  • Loss of one phase on the drive output terminals (U, V, or W)
  • Poor or loose connections from the drive to the motor
  • Faulty or damaged motor cable insulation or conductors
  • Issue with a downstream contactor, such as an open contact, incorrect connection, or damaged cable

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check all power connections between the ATV310 drive output terminals (U, V, W) and the motor terminals for tightness and integrity.

  2. 2

    Inspect the motor power cables for any signs of physical damage, nicks, or breaks in insulation.

  3. 3

    If a downstream contactor is used, verify its wiring, contact integrity, and proper operation during run conditions.

  4. 4

    Measure the voltage at the drive output terminals (phase-to-phase) with the drive enabled to confirm all three phases are present and balanced.

Alle Codes in diesem Handbuch durchsuchen (37)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Schindler Easy Altivar ATV310 Drive