OP2
Overvoltage During Deceleration
Schindler · Altivar 212 Variable Frequency Drive
Was bedeutet OP2 ?
This fault indicates an overvoltage condition during motor deceleration by the Altivar 212 drive, possibly due to excessively short deceleration times, overhauling loads, or fluctuating input voltage.
Häufige Ursachen
- Deceleration time is too short (dEC or F501).
- Overhauling load on the motor.
- Input voltage is fluctuating abnormally.
- Power network capacity is greater than 200 kVA.
- Power factor capacitor switching in the supply network.
- SCR switching on the power network.
- Drive is starting into a rotating load.
- Intermittent output phase fault.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Increase the deceleration time parameters (dEC or F501).
- 2
Enable parameter F305 ([Overvoltage fault]) for overvoltage prevention.
- 3
Install a line reactor to mitigate input voltage issues.
- 4
Check the input and output circuits for phase loss detection and rectify.
- 5
Enable catch on the fly function (F301).