CFI2
Download Transfer Fault
Schindler · Altivar 212 Variable Frequency Drive
Was bedeutet CFI2 ?
This fault occurs when the Altivar 212 drive's configuration is invalid or inconsistent, typically after a configuration download via PC software. It can also indicate an unsuccessful transfer due to rating differences between the source and target drives (e.g., uploading an ATV212N4 configuration to an ATV212M3).
Häufige Ursachen
- Invalid or inconsistent configuration loaded into the drive.
- Configuration transfer using PC software failed due to rating mismatches.
- Detected fault during an interruption of download configuration transfer.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the previously loaded configuration for consistency and compatibility.
- 2
Load a compatible configuration that matches the drive rating.
- 3
Before performing a download with PC software, uncheck "Display communication error" in the Tool / Environnement option / Startup/Comm. settings.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026