Etn1
Auto-tuning Fault
Schindler · Altivar 212 Variable Frequency Drive
Was bedeutet Etn1 ?
This fault indicates a failure during the Altivar 212 drive's auto-tuning process, which can be caused by incorrect motor parameters, an oversized motor, an undersized cable, or the motor not being completely stopped.
Häufige Ursachen
- Parameters F401 ([Slip Compensation]) to F494 ([Mot. adj coefficient]) are incorrectly set.
- The motor is too large for the drive.
- The motor cable gauge is too small.
- The motor is still rotating at the start of the auto-tune.
- The drive is not powering a 3-phase induction motor.
- Measured current at initial position detection during auto-tuning is too small or large according to motor inductance or output phase loss.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify and set parameters F401–F494 correctly.
- 2
Ensure the drive is properly sized for the motor.
- 3
Use a motor cable with the correct gauge for the application (e.g., ensure leads are less than 30 m).
- 4
Verify that the motor is completely stopped and de-energized before initiating auto-tune.
- 5
Ensure the drive powers only a 3-phase induction motor for auto-tuning.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026