Übersetzen...
EPH0
Output Phase Loss Fault
Schindler · Altivar 212 Variable Frequency Drive
Was bedeutet EPH0 ?
This fault is detected when one or more output phases to the motor are lost, leading to an imbalance or interruption in motor current from the Altivar 212 drive. This can severely affect motor operation and cause damage.
Häufige Ursachen
- Loss of one or more output phases.
- Bad connection in the output circuit (U, V, W terminals).
- Output disconnect has opened.
- Open winding in the motor.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect motor cable connections at the drive's output terminals (U/T1, V/T2, W/T3) for tightness and continuity.
- 2
Measure the resistance of motor windings to identify an open circuit.
- 3
Verify the status of any output disconnect devices (e.g., motor contactor).
- 4
Check parameter F605 ([Output phase loss]) setting.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Schindler Altivar 212 Variable Frequency Drive