Übersetzen...
0201

No Origin Input Signal

Omron · SYSMAC CJ Series PLC

Was bedeutet 0201 ?

This fault occurs during an origin search when the main origin input signal was not received. This prevents the system from precisely determining its home position, indicating a failure to detect the final origin marker.

Häufige Ursachen

  • Faulty wiring of the origin input signal, leading to an open circuit or poor connection.
  • Incorrect 'Origin Input Signal Type' (NC or NO) configured in PLC Setup.
  • Origin sensor failure, damage, or mispositioning, preventing proper detection.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Visually inspect the wiring connections for the origin input signal for integrity; measure continuity of the cable from sensor to input terminal.

  2. 2

    Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and verify the 'Origin Input Signal Type' setting is correctly configured (NC or NO) to match the sensor's operation.

  3. 3

    Test the origin input sensor operation by manually activating it and verifying the corresponding input signal status at the PLC input terminal.

  4. 4

    Ensure the physical positioning of the origin input sensor allows for proper detection during an origin search.

  5. 5

    Initiate an origin search again from the HMI or programming software.

Alle Codes in diesem Handbuch durchsuchen (20)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes